MPC
Shopping Cart
(0 Items) £0.00

LOWARA GLV 65-42-253

LOWARA GLV 65-42-253 Go back »
Description:

APPLICATIONS
• The Lowara GLV series submersible pumps are for pumping clean water, surface water
and wastewater containing solids or long-fibred material.
The vortex impeller is the best choice in low volume, high
head applications and in media which contains sand and
other abrasive solids.

 Q = DELIVERY
Pump TypePgr (P1) kW *(P2) Nom kW **D Impeller mmMin-1l/s    024681012,51520253035404554
m³/h 07,214,421,628,836,045547290108126144162196
H = TOTAL HEAD METRES COLUMN OF WATER
GLV 65-15-2512,01,510529008,37,05,64,33,3----------
GLV 65-15-2532,01,610529008,47,15,74,53,4----------
GLV 65-20-2532,52,0117290010,99,58,06,45,13,5---------
GLV 65-24-2533,22,4129290013,612,210,79,17,65,73,6--------
GLV 65-32-2533,83,2138290016,315,213,711,910,07,75,9--------
GLV 65-42-2535,34,2155290019,918,717,115,213,210,88,85,7-------



SPECIFICATIONS
• Delivery: up to 200 m3/h.
• Head: up to 29 m.
• Free passage: up to 100 mm.
• Discharge connection:
DN 50 - 65 - 80 - 100 mm.
• Motor power: up to 7,4 kW.
• Maximum liquid temperature:
40 °C.
• Maximum immersion depth: 20 m.
• pH pumped liquid: pH 5,5-14.
• Maximum liquid density:
1100 Kg/m3.
• Motor with IP68 protection and
class H insulation (180°C).
• Power supply 230V single-phase,
400V three-phase, 50 Hz.
• Voltage variation:
- continuous running: max ±5%.
- intermittent running: max ±10%.
• Voltage imbalance between phases:
max 2%.
Maximum number of starts per hour:
30.
/images/tricel_home_banner
/images/free_delivery_banner
/images/price-match-guarantee_3
/images/new_offers_ksb501_1
/images/new_offers_conversionkit
/images/servicing_side_box_2
/images/need_advice_side_box
/images/sagepay_side_box
/images/join_us_on_facebook